What is the load center length for a branch circuit with noncontinuous loads of 20A at 60' from the source and 50A at 125' from the source?
a. 106.43'
b. 125.12'
c. 136.56'
d. 157.95'
a. 106.43'
20A x 60' = 1,200
50A x 125' = 6,250
Find the sum of the results, and divide it by the sum of the individual loads:
1,200 + 6,250 = 7,450
20A + 50A = 70A
7,450 รท 70A = 106.43'
You might also like to view...
In a given length of pipe, if the flow rate in gallons per minute (gpm) is doubled, pressure drop _____
a. stays the same b. doubles c. quadruples d. increases slightly
The faster a shock absorber moves the more resistance it has to the movement
a. true b. false
Show calves should be brushed at least how often with a soft brush?
A. three times daily B. once daily C. twice weekly D. once weekly
Voltage divider bias provides a high degree of stability as long as what principle is observed?
A) IR2 is ten times greater than IB. B) RL is smaller than R1 + R2 C) IB = IR2 D) Either a or b