What is the load center length for a branch circuit with noncontinuous loads of 20A at 60' from the source and 50A at 125' from the source?

a. 106.43'
b. 125.12'
c. 136.56'
d. 157.95'


a. 106.43'
20A x 60' = 1,200
50A x 125' = 6,250
Find the sum of the results, and divide it by the sum of the individual loads:
1,200 + 6,250 = 7,450
20A + 50A = 70A
7,450 รท 70A = 106.43'