The maximum size dual-element fuse for a 40hp, 3Ø, 460V motor with a Design Letter D is _____.

a. 60A
b. 100A
c. 125A
d. 175A


b. 100A
52A (see NEC Table 430.250) x 1.75 (see NEC Table 430.52) = 91A
Next standard size per NEC Section 240.6(A) is 100A