How did the factor used in the determination of conductor size change with the 2011 changes to the Code?

What will be an ideal response?


In the case of a wye-start, delta-run motor, the previous edition of the Code did not include a factor of 1.25 in the determination of the conductor size for the conductors between the controller and the motor. In the past, the instruction was to use 0.58 times the motor full-load current.