Briefly discuss panelboard installations that do not require a main protective device and then outline situations in which individual protection is required.

What will be an ideal response?


Panelboards are available with standard main ratings of 100, 225, 400, 600, 800, and 1200 amperes. These panelboards may be installed without a main protective device and can be connected directly to a feeder protected at not more than the rating of the panelboard. Individual protection is required on lighting and appliance panelboards when these panelboards are connected to the secondary of a transformer having only primary protection.