A technician takes the following readings while checking the operation of an electric furnace with 2 heat strips: 220 volts, 36 amps, 70°F return air temperature, and 120°F supply air temperature. What is the airflow through the furnace?

A) = = 540 CFM B) = = 158 CFM
C) = = 500 CFM D) (120 - 70 ) × 1.08 × 10 = 540 CFM


C

Trades & Technology

You might also like to view...

Explain why a prefabricated steel stair is most commonly used even in buildings that are built with a reinforced-concrete frame structure.

What will be an ideal response?

Trades & Technology

Using the wrong lubricant in a manual transmission could cause all of these EXCEPT ________.

A) Slipping clutch B) Damage to the composite blocker rings C) Hard shifting D) Damage to bearings

Trades & Technology

Among the fundamental tenets of the late medieval Roman Catholic Church that English theorist John Wyclif rejected was

a. scholasticism. b. science and mathematics. c. the divine nature of Christ. d. the seven sacraments.

Trades & Technology

What information is necessary to determine a system balance point?

A) A heat load calculation and the system capacity at two operating conditions B) The balance point is determined as part of the heat load study before the equipment is chosen. C) The balance point for all AHRI rated heat pumps is 35°F. D) The manufacturer's installation instructions, which publish the equipment balance point