If a service entrance is rated at 200 amperes, the service entrance conductor size would be a minimum of 2/0 copper or 4/0 aluminum. According to Table 250.102(C)(1) the minimum grounded conductor or bonding jumper size would be _____ AWG.

a. 1
b. 2
c. 3
d. 4


d. 4