The manufacturer's data on a split AC system indicates that the normal temperature drop should be 15°F at the current operating conditions. If the evaporator entering air temperature is 80°F and the leaving air temperature is 55°F, the technician knows that the system:

A) Most likely is overcharged because it is cooling better than it is supposed to.
B) Is working great, even better than manufacturer's specifications.
C) Most likely has higher than normal airflow because of the higher-than-normal temperature drop.
D) Most likely has low air flow because of the higher-than-normal temperature drop.


D