For a low-temperature refrigeration system with an evaporator saturation temperature of -40°F, why might R-502 be used instead of R-12?

What will be an ideal response?


R-502 would keep the suction pressure positive (above atmospheric pressure), while and R-12 system would operate with the suction pressure in a vacuum (below atmospheric pressure).