What requirements should be followed for lighting and appliance panelboards?

What will be an ideal response?


For these panelboards, follow these requirements:

?The panelboard shall have a rating of not less than the minimum feeder capacity as calculated according to NEC Article 408.
?The panelboard must be protected using an overcurrent protective device with a trip setting not exceeding the rating of the panelboard.
?The total 3-hour load shall not exceed 80 percent of the panelboard rating except when specifically rated for 100 percent continuous duty.