How does a "pressure sandwich" work for smoke control?
A) The fire floor is held neutral and the floors above and below are exhausted to remove smoke.
B) The fire floor is made positive to drive smoke up a shaft, floors above and below are neutral.
C) The fire floor is exhausted to and floors above and below are pressurized.
C) The fire floor is exhausted to and floors above and below are pressurized.
You might also like to view...
The production possibilities curve in the current period
A) Reflects only the most efficient combinations of two products to generate revenue. B) Reflects only the most efficient combination of two inputs to generate revenue. C) Reflects all of the combinations of two products to generate revenue. D) None of the above
Before using any corded power tool, make sure it is _____.
a. equipped with a surge protector b. properly grounded c. OSHA approved d. equipped with an On-Off switch
In the accompanying figure, the item identified as number 2 is the ____.
A. line of sight B. top view C. lines of projection D. front view
A single-phase electrical device in a building draws 37 A and is supplied with two type THWN copper wires in a conduit. The conduit is run up through the cores of concrete blocks in a building. The wire ampacity is to be sized at 125% of the 37 A, which is 46.25 A. The minimum size of wire permitted is AWG number ____.
A. 4 B. 6 C. 8 D. 10