Determine the minimum number of 15-ampere, 120-volt lighting circuits required for a 1200 square foot apartment.
What will be an ideal response?
1200 square feet X 3 volt-amperes per square foot =3600 volt-amperes
amperes=watts/volts=3600/120=30 amperes
30 amperes/15 amperes per circuit=2 lighting circuits required
You might also like to view...
The internal resistance of any meter is only effective if the meter is set on the ________ scales
A) Ammeter B) Voltmeter C) Ohmmeter D) None of these
Which of the following statements about bonding is not true?
A. Bonding completes a path for fault current to flow through. B. Bonding conductive parts together keeps the conductive materials at the same electrical potential. C. Bonding’s primary purpose is to make an earth connection. D. Bonding has the effect of eliminating any shock hazard between bonded enclosures or parts.