The manufacturer's data on a split AC system indicates that the normal temperature drop should be 15°F at the current operating conditions. If the evaporator entering air temperature is 80°F and the leaving air temperature is 55°F, the technician knows that the system
A) Is working great, even better than manufacturer's specifications
B) Most likely is overcharged because it is cooling better than it is supposed to
C) Most likely has low air flow because of the higher than normal temperature drop
D) Most likely has higher than normal airflow because of the higher than normal temperature drop
C
You might also like to view...
The transmission’s output shaft and its sealing components are being discussed: Technician A says the shaft and all of its sealing components must be replaced if nicks and scratches are found in the shaft’s sealing area. Technician B says all of the shaft’s seals and rings must be replaced during a rebuild. Who is correct?
A. A only B. B only D. Neither A nor B
When cutting pipe, you must always transfer _____ to the cut pieces.
a. the brand name b. the heat number c. the burr d. the number of cuts
All of the following were results of the Fugitive Slave Act of 1850 EXCEPT
A. many people were drawn into the antislavery movement. B. Northerners who aided slaves in escaping faced heavy fines and jail sentences. C. federal commissioners handling the cases of runaways received twice as much in a bonus if the slave was returned. D. Northerners protested the capture of individual runaway slaves. E. the Underground Railroad scaled back its efforts.
Work environments with a lack of technical-excellence incentives can positively influence the entrepreneurial intentions of some employees.
Answer the following statement true (T) or false (F)