In the accompanying figure, what happens when the DOWN button is pressed?



What will be an ideal response?


When the DOWN push button is pressed, control relay CR energizes. The normally closed CR contacts connected in series with M contactor opens to interlock the circuit, and the normally open CR contact connected in series with the solenoid coil closes.