How do you determine conductor size for a single motor?
What will be an ideal response?
NEC Section 430.6(A)(1) states that the conductor for a motor connection shall be based on the values from Tables 430.247, 430.248, 430.249, and 430.250 instead of the motor nameplate current. Section 430.22(A) states that conductors supplying a single motor shall have an ampacity of not less than 125 percent of the motor full load current. NEC Section 310 is used to select the conductor size after the ampacity has been determined. The exact table employed will be determined by the wiring conditions. Probably the most frequently used table is 310.16.
You might also like to view...
Describe and evaluate the content and conduct of Eisenhower's vice-presidential running mate Richard Nixon in his political attacks on and assertions about the Democratic candidate Adlai Stevenson? How did Nixon's political background make him an apt choice to make the type of hyperbolic and fiercely ideological political attacks on Stevenson that ultimately weakened the Democratic presidential candidate in the general election?