Which of the following could cause this condition?

A walk-in freezer with TEV has the following conditions:
? Subcooling is 10°
? Superheat is 0°

a. Dirty or iced evaporator
b. Blocked liquid line filter drier
c. Overcharge
d. Undercharge


a. Dirty or iced evaporator (FLOODING, TEV LOST CONTROL)

? Subcooling is 10° NORMAL
? Superheat is 0° LOW

Trades & Technology

You might also like to view...

Technician A says on some Chrysler transaxles the solenoid/pressure switch is a single unit that consists of various solenoids and pressure switches. Technician B says on some General motors transmissions the fluid pressure switch assembly contains five different pressure switches and is connected to five different hydraulic circuits. Who is correct?