A three-phase wye-connected load is connected to a 480 V three-phase line. The line current is 36 A. If this load is purely resistive, what is the total amount of power being used in this circuit?

A. 51.84 kW
B. 29.93 kW
C. 7.48 kW
D. 12.96 kW


Answer: B