You are asked to install a water heater, rated at 3-kW, 240 V. Calculate the load in amperes, and determine the branch-circuit ampere rating.

What will be an ideal response?


Since, The CodeĀ® requires the water heater rating of not less than 125% :
amperes=(watts*1.25)/volts
amperes=(3,000*1.25)/240
amperes=3,750/240=15.6A
Therefore, the branch-circuit ampere rating should be 20A.