During a flow test, a single 2 1/2-inch hydrant outlet is flowed. The actual diameter of the discharge measures 2 5/8 inches (2.625 inches) with a C factor of 0.80 . The flow pressure measured by the pitot gauge is 54 psi. What is the volume of water flowing from this discharge?
What will be an ideal response?
1,208 gpm