A commercially available three-phase inductive motor operates at a full load of 120 hp (1 hp = 746 W) at 95% efficiency at a lagging power factor of 0.707. The motor is connected in parallel to a 80-kW balanced three-phase heater at unity power factor. If the magnitude of the line voltage is 480 V (rms), calculate the line current.

What will be an ideal response?