A house will have an electric range that has a nameplate rating of 11.5 kW. What is the branch circuit load for the range?
What will be an ideal response?
The first sentence in Note 4 to Table 220.55 says that it is permissible to use Table 220.55 to calculate the branch circuit load for one range. Use column C of Table 220.55 to get the maximum demand in kilowatts of a range not over 12 kW in rating. The first row is used when there is one range in a house. Because the range being installed is rated at 11.5 kW, use row 1, column C, which indicates that 8 kW is the value to be used for one range that has a rated value of 12 kW or less.
You might also like to view...
One way to recover invested capital with interest is to collect the principal P over n years as P?n and also collect the interest on the unrecovered balance. Assume you borrowed $6000 at 10% per year interest with a repayment period of 3 years to purchase a new network controller for your company. (a) Use the method above to determine the amount of each of the three payments. (b) Determine the amount of each payment if they are all equal.