In a 2-ton TX valve system, the unit does not develop full capacity. Head pressure is high, suction pressure is slightly above normal, and subcooling is below normal. What is the problem?
What will be an ideal response?
The problem is a dirty air-cooled condenser or plugged water-cooled condenser.