How do you select a fuse with the correct continuous current rating to provide transformer protection?

What will be an ideal response?


The selection of the fuse with the correct continuous current rating to provide transformer protection is based on the following recommendations:

?select a fuse with the lowest rating that has a minimum melting time of 0.1 second at 12 times the continuous current rating of the transformer;
?select a fuse with a continuous current rating of 1.6 times the continuous current rating of the transformer;
?select a fuse that complies with NEC Article 450.