The compressor in an existing split system is being replaced. The system has a 35 foot line set. The factory charge for the condensing unit is 80 ounces. The installation instructions state that the factory charge assumes a line length of 15 feet and gives the per foot adjustment as 0.6 ounces per foot. How much refrigerant should be added to the system after the system has been evacuated?
A) 80 ounces B) (35-15 ) × 0.6 = 12 ounces
C) 80 ounces + (35 × 0.6 ) = 101 ounces D) 80 ounces + ((35-15 ) × 0.6 ) = 92 ounces
D
You might also like to view...
The term ____ is commonly used in architectural CADD applications to refer to any text, notes, dimensions, and text symbols on a drawing.
A. dimension B. annotation C. construction D. amendment
Match the type of pipe fitting to the description:
I. Plug II. Cap III. Bushing IV. Flange a. Used to close (seal) the open end of a pipe; may be threaded, glued, or welded. b. Threaded on both the internal and external surfaces; used to join two pipes of differing sizes. c. Consists of a mating plate used to join two pieces of pipe or a valve to a piece of pipe. d. Used to close the end of a piping run; the threading is male and fits into a female-threaded fitting; can be glued, threaded, or welded into place.