Explain a method used to determine the correct operating discharge pressure of a commercial refrigeration system

What will be an ideal response?


The method used is as follows:
Step 1 – Measure the dry-bulb temperature of the air entering the condenser. (We will refer to this as the EAT – Entering Air Temperature).

Step 2 – Measure the system's operating suction pressure.

Step 3 – Using a Pressure/Temperature (P/T) chart, convert the suction pressure to its equivalent saturation temperature.

Step 4 – Determine the system's application: low temperature, medium temperature, or high temperature. A low temperature system is one that operates at an evaporating temperature of 0°F and below. A medium temperature system is one that operates at an evaporating temperature of between 0°F and 25°F. A high temperature system is one that operates at an evaporating temperature of between 25°F and 45°F.

Step 5 – Using the chart below, determine the appropriate Temperature Rise (TR). The TR is the difference between the EAT and the condensing temperature of the refrigerant in the condenser.

Step 6 – The Condensing Temperature

Trades & Technology

You might also like to view...

? Identify and state the historical significance of Thomas Paine.

What will be an ideal response?

Trades & Technology

What is the difference between a cherry picker and an engine sling?

What will be an ideal response?

Trades & Technology

When a sliding fifth wheel is used on a tractor, which position would most likely provide the driver with the most comfortable ride?

A. full travel forward B. over the bogie centerline C. slightly behind of the bogie centerline D. full travel rearward

Trades & Technology

The quantity of air a blower is moving is measured in:

A) Feet per minute - FPM. B) Capacity per minute - CFM. C) Cubic feet per minute - CFM. D) Force per minute - FPM.

Trades & Technology