Which of the following statements is correct about sizing the supply-side bonding jumper on the line or supply side of the service equipment?

A. It is sized from Table 250.66 in accordance with the size or rating of the overcurrent
protective device in the service equipment.
B. It is sized from Table 250.122 in accordance with the size rating of the overcurrent
protective device in the service equipment.
C. It is sized from Table 250.102(C)(1) in accordance with the size of the service-entrance
conductors on the supply side of the service.
D. It is sized from Table 250.122 in accordance with the size of the service-entrance
conductors on the supply side of the service.


C. It is sized from Table 250.102(C)(1) in accordance with the size of the service-entrance
conductors on the supply side of the service.