How are machinery space refrigerant sensors maintained?

What will be an ideal response?


For routine maintenance, sensors should be exposed to a refrigerant sample on a monthly basis to ensure they are operating correctly. This will also provide a check for the visible and audible alarms. Infrared sensors should have signal voltages measured and logged on a regular basis. Calibration should be performed with certified calibration gas every six months.