If a 120V feeder for nonmotor loads feeds a continuous load rated at 20A and a noncontinuous load at 30A, what size overcurrent protective device should be selected?
a. 45A
b. 60A
c. 70A
d. 80A
b. 60A
20A x 1.25 = 25A
25A + 30A = 55A; size up to 60A
You might also like to view...
Two technicians are discussing compression test results. Technician A says that abnormally low compression in adjacent (neighboring) cylinders most likely indicates a bad head gasket. Technician B says that if the reading on the compression tester goes up after adding oil to the cylinder, the compression rings are probably worn. Who is right?