What is the advantage of a case coil secondary loop system?
What will be an ideal response?
The primary refrigerant is used for cooling the glycol in the chiller and is not delivered to the individual cases. This eliminates the need for long pipe runs of refrigerant as required in multiplex direct expansion systems that considerably reduces the amount of charge required. Long refrigerant runs of multiplex systems incur large pressure drops and result in high suction gas superheat. These conditions reduce the mass flow rate of the compressors that results in loss of refrigeration capacity for multiplex systems.
You might also like to view...
Answer the following statements true (T) or false (F)
1) Psychosomatic reaction to stress may eventually lead to autoimmune disease. 2) The effects of stress can become pathological after they exceed a person's coping limits. 3) Efforts to rid the workplace of all sources of stress are likely to fail. 4) Employees cannot be taught to adapt to stress in the workplace. 5) Three stages of human reaction to stress are: 1) alarm, 2) resistance, and 3) exhaustion.