List some common causes of an evaporator operating with a low superheat and a high suction pressure

What will be an ideal response?


Some common causes of an evaporator with a low superheat and a high suction pressure are:
oversized valve TXV seat is leaking

low superheat adjustment
sensing bulb making poor thermal contact wrong thermostatic charge
incorrectly located external equalizer