Wire type THWN copper is run in a raceway from a wall outlet in a building under concrete floor where the conduit is in contact with the earth. The walls are exposed on both sides to free air. If the load requires a minimum wire rating of 75 A, the minimum wire size permitted is ____ AWG.

A. 4
B. 6
C. 8
D. 10


Answer: A