In Figure 39-46, list the sequence of events that occur when the cooling relay is energized
What will be an ideal response?
The NO cooling relay contacts on line 14 close to energize the outdoor fan contactor.
The outdoor fan contactor NO contacts on line 5 close to energize outdoor fan motor 1.
The outdoor fan contactor NO contacts on line 8 close. If the high pressure control closes, outdoor fan motor 2 will energize.
The NO cooling relay contacts on line 12 close to energize the compressor contactor.
The compressor contactor closes to energize the compressor.
You might also like to view...
¿Qué sistema de conductos está corriente abajo de una caja terminal?
a. Uno de baja presión b. Uno de conducto dual c. Uno de alta presión d. Uno de presión media
Sensitive areas of the horse include all of the following except:
A. legs B. neck C. mouth D. flanks
Which component is NOT a safety requirement for steering column systems?
A) Collapsible column B) Sector shaft C) Knee bolster D) All of these are correct.
The <> symbol is called the ____________________ operator.
Fill in the blank(s) with the appropriate word(s).