What is the total available static pressure for the ductwork in a system with the following specifications?
Blower: 0.6" WC total external static at design airflow
Evaporator Coil: 0.25 in WC static pressure drop at design airflow
Filter: 0.15 in WC static pressure drop at design airflow
Registers and Grills: 0.05" WC static pressure drop at design airflow
A) 0.15 in WC available static pressure B) 10 in WC available static pressure
C) 0.6 in WC available static pressure D) 0.25 in WC available static pressure
A