Determine the pump discharge pressure required to adequately supply a portable master stream device equipped with a 750 gpm fog nozzle. This device is being supplied by two 2 1/2-inch hoselines and one 3-inch hoseline with 2 1/2-inch couplings, each 250 feet long

What will be an ideal response?


123 psi