What overload protection is required for the motors of the fan coil units in the cooling equipment?
What will be an ideal response?
The motors of the fan coil units can be expected to run for continuous periods of time exceeding 3 hours. Thus, these motors are considered to be continuous duty motors. Overload protection must be provided for the motors and is sized as follows:
? | a separate overload device for each motor; |
? | a device that is selected as follows: |
- | for motors with a service factor of not less than 1.15, the device rating is 125 percent Full Load Amps (FLA). |
- | for motors with a temperature rise of not over 40C, the device rating is 125 percent FLA. |
- | for all other motors, the device rating is 115 percent FLA. |
You might also like to view...
Which of the following statements is true regarding the energy-recovery wheel?
A) The energy-recovery wheel does not allow more indoor air into the system without significantly increasing operating costs. B) The energy-recovery wheel does not rotate when exiting air passes through it. C) The energy-recovery wheel mixes outdoor and exhaust air as the air streams pass through it. D) The energy-recovery wheel is configured so that exhaust air exits the top and outdoor air enters the bottom.