What rules apply when you are using parallel feeders?

What will be an ideal response?


Several rules must be followed when using parallel feeders:

?all phase conductors, and the neutral if used, as well as all equipment grounding conductors must be grouped in each raceway;
?the conductors must be 1/0 AWG or larger;
?the conductor in one grouping must be the same length, the same conductor material, the same size, have the same type of insulation, and be terminated in the same manner as the conductors in the other grouping(s); and
?the raceways containing the groups of conductors must have the same physical characteristics.