A feeder circuit with no motor load has a continuous load of 10A and a noncontinuous load of 10A. The feeder overcurrent protective device should be sized at _____.

a. 12.5A
b. 20A
c. 22.5A
d. 27.25A


c. 22.5A
Nonmotor feeder load = 125% of the continuous load + 100% of the
noncontinuous load = (10A x 1.25) + 10A = 22.5A