How would the primary control need to differ to accommodate power venting?

What will be an ideal response?


Power venting systems require that the furnace primary control allows for a delayed burner firing at startup. This allows the vent blower to come on and produce a draft before the burner firing sequence begins. The blower must also continue to run for a period of time after the burner shuts down to insure venting of all the combustion gases.