Calculate the following:
A three-phase, six-pole, Y-connected, 60 Hz, 480 V induction motor is driving a
300 Nm constant-torque load. The motor has rotational losses of 1 kW. The motor
is driven by a slip energy recovery system. The triggering angle of the dc/ac
converter is adjusted to 100o
a. Motor speed
b. Current in the dc link
c. Rotor rms current
d. Stator rms current
e. Power returned back to the source